BX Series

BXN

type loghi certificazioni bxn bxc bxa type bx series rcn

Flameproof Ex d ˙ increased safety Ex e ˙ for indoor & outdoor applications

for Unarmoured cables
foto BXN type BX series rcn
schema BXN type components options BX series rcn

Cable glands BXN type
(code: BXN)

The cable glands of the BXN series have been designed for sealing one or more cores. It has a body which houses the container intended to contain the epoxy resin for sealing the cores. Above the container is positioned a spacer whose function together with the backnut that is going to be screwed onto the body of the cable gland is to lock the container in position.

Application fields

Surface - Group II ˙ Mines - Group I

Approvals / Certifications

ATEX: CESI 14ATEX069X
IEC Ex: IECEx CES 15.0001X
EAC: RU C-IT.A 45.B.00081

Protection type

Exd IIC • Ex e II (gas) • Ex tb IIIC (dusts) • Ex d I • Ex e I (mines)

EPL (Equipment protection level)

Zone 1-2: Mb mines • Gb, Gc gas
Zone 21-22: Db Dc combustible dusts

Execution

Ex d IIC • Ex e II • Ex tb IIIC • Ex d I • Ex e I Db
according to
ATEX: EN 60079-0:2009 •  EN 60079-1:2007 • EN 60079-7:2007 •
EN 60079-31:2009 • EN 60529:1991
IEC Ex: IEC 60079-0:2011 • IEC 60079-1:2007 • IEC 60079-7:2006 • IEC 60079-31:2008 • IEC 60529:2001

Ambient temperatures range:

-60°C ÷ +110°C

Service temperatures range:

-60°C ÷ +130°C

Cable type

Unarmoured

Available materials

Brass (code: OT) • Nickel-plated brass (code: ON)
AISI316L Stainless steel (code: S6) • Aluminium (code: AL)

Available threads

ISO 262 Metrical • ISO 228 • DIN 40430 Pg
ANSI B1.20.1 NPT • EN 10226 Gk (only for ATEX)

Degree of protection

The cable glands degree of protection is IP66 or IP66/68, 30-meters depth for 7 days according to the IEC EN 60529 standard; the degree of protection IP 68 is obtained by using flat sealing rings on cable glands with cylindrical threads. Without gaskets, the degree of protection is IP 66. If the cable glands with cylindrical or tapered threads are screwed on the threaded hole of an apparatus, in order to guarantee an IP66 or IP66/68 degree of protection, threaded parts must be sealed with Loctite or similar. In order to maintain the IPX8 degree of protection,  the cable entry shall be fitted on enclosure witch satisfies an immersion test under 30 meters of water during 7 days. Metric cable glands are made in accordance to 
EN 62444 Standard.

Mix solid compound BXN BXC BXA type bx series rcn

COMPOUND

Application
Mixing time
Gel time
Full cure time
Installation

SOLID

By hand
30 min
-
4 hours
Any Orientation

DESIGNED FOR SEALING ONE OR MORE CORES

Example Code

example code bxn type table
example code bxn type table ot on sa al

Technical Drawing

technical drawing bxn type
BXN type table details